Skip to main content Skip to navigation

EcoPure Refrigerants

  • Refrigerant grade propane (R-290) and isobutane (R-600a)
  • Meets AHRI 700 Standard - 99.5% purity level
  • Non-odorized
  • Reusable canister – use contents to completion
  • EcoPure Charging Assembly is the most simple, reliable, and accurate approach in the market!
  • EcoPure Charging System provides integrated charging hose and shut-off valve with precision weigh scale for simplified and accurate charging

Description:

EcoPure R-290 and R-600a are refrigerant grade products that meet AHRI 700 Standard purity requirements. The EcoPure refrigerants are colorless and non-odorized, so extreme care is required when handling these refrigerants.EcoPure R-290 and R-600a refrigerants are approved by the EPA’s SNAP program for the US market, effective April 2015 for food service applications. EcoPure refrigerants are for qualified professionals and only for equipment specifically designed and clearly identified that it uses R-290 or R-600a refrigerant.

Although these refrigerants are highly flammable, they are eco-friendly. Both R-290 and R-600a refrigerants have zero ozone depletion potential (ODP) and global warming potential (GWP) of three or less. In addition to EcoPure’s low environmental impact, they are more efficient than the HFC refrigerants they replace. Improved system efficiency reduces energy usage and life cycle costs.

The EcoPure Charging Assembly is the simplest, most reliable and accurate method for charging R-290/R-600a systems in the market. The EcoPure Charging Assembly allows the ability to recharge the system with one gram accuracy!

For contractors servicing small refrigeration systems who need a charging scale, the EcoPure Refrigerant Charging System has everything they need for precision dispensing and maximum flexibility at the job site. 

Packaging Size Part Number Additional Info
R-600a Refrigerant 4175-31 10.6 oz. canister
R-600a Refrigerant (Discontinued) 4175-30 14.8 oz. canister
R-290 Refrigerant 4175-21 10.6 oz. canister
EcoPure Charging Assembly 4175-10 1 each
EcoPure Refrigerant Charging System 4175-11 1 each

Directions:

FOR USE BY QUALIFED PROFESSIONALS ONLY.

ALWAYS USE IN ACCORDANCE WITH COMPLETE SERVICE INSTRUCTIONS DETAILED BY THE SPECIFIC EQUIPMENT MANUFACTURER.

1. Wear protective gear, use hydrocarbon gas monitor, and reaffirm no ignition sources.

2. Pull vacuum through suction service port, then isolate system to ensure it’s leak free.

3. Ensure hand valve is closed. Invert charge base and connect to upright EcoPure canister.

4. Crack hand valve to purge line while fastening to valve isolating the evacuated system. IMPORTANT: Always charge through the low side of system. Never expose EcoPure canister to high side pressure.

5. Invert cylinder/assembly on weigh scale for liquid refrigerant charging. Purge hose, tare scale, slowly charge to OEM specification. If necessary, briefly cycle system to fully charge. Do NOT overcharge.

6. Close assembly hand valve after charging. In a ventilated area, turn the canister upright, quickly remove from charging base and follow manufacture guidelines to seal the process tube.

Product Information:

Literature Downloads

Download the product bulletin and other relevant literature here.

Labels

Download a low resolution file of the product label here.

Product Safety

RTK Information

2611 Schuetz Rd. St. Louis, MO 63043
  • Telephone: 800.554.5499
  • Email: info@nucalgon.com
  • Hours: Mon–Fri: 8:00am - 5:00pm (Central Time)

We'd love to hear from you.

We'd love to hear from you.

Click the box to submit